بریر دیجیتال مدل KCD2-ST-EX2 مارک PEPPERL FUCHS آلمان با ورودی 2 کانال دیجیتال( و رودی کنتاکت یا نامور) و خروجی 2 کانال دیجیتال ترانزیستوری جهت استفاده در پروسه های ابزار دقیق و اتوماسیون در محیط های ضد انفجار یا HAZARDOUS AREA به کار میرود.
214243_eng | 366٫36 کیلوبایت | دانلود |
Switch Amplifier
KCD2-ST-Ex2
General specifications | ||
Signal type | Digital Input | |
Supply | ||
Connection | Power Rail or terminals 9+, 10- | |
Rated voltage | 19 ... 30 V DC | |
Ripple | ≤ 10 % | |
Rated current | 30 ... 20 mA + Iout | |
Power loss | ≤ 800 mW including maximum power dissipation in the output | |
Input | ||
Connection | terminals 1+, 2-; 3+, 4- | |
Rated values | acc. to EN 60947-5-6 (NAMUR) | |
Open circuit voltage/short-circuit current | approx. 10 V DC / approx. 8 mA | |
Switching point/switching hysteresis | 1.2 ... 2.1 mA / approx. 0.2 mA | |
Line fault detection | breakage I ≤ 0.1 mA , short-circuit I ≥ 6.5 mA | |
Pulse/Pause ratio | min. 100 µs / min. 100 µs | |
Output | ||
Connection | terminals 5, 6 | |
Rated voltage | 30 V DC | |
Rated current | 50 mA | |
Response time | ≤ 200 µs | |
Signal level | 1-signal: (supply voltage) - 3 V max. for 50 mA 0-signal: blocked output (off-state current ≤ 10 µA) |
|
Output I | signal ; Transistor | |
Output II | signal ; Transistor | |
Collective error message | Power Rail | |
Transfer characteristics | ||
Switching frequency | ≤ 5 kHz | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2004/108/EC | EN 61326-1:2006 | |
Conformity | ||
Electromagnetic compatibility | NE 21:2011 | |
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Mass | approx. 100 g | |
Dimensions | 12.5 x 114 x 119 mm (0.5 x 4.5 x 4.7 in) , housing type A2 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with Ex-areas | ||
EC-Type Examination Certificate | BASEEFA 13 ATEX 0080 | |
Group, category, type of protection | II (1)G [Ex ia Ga] IIC II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I |
|
Statement of conformity | PF 13 CERT 2760 X | |
Group, category, type of protection, temperature class | II 3G Ex nA IIC T4 Gc | |
Directive conformity | ||
Directive 94/9/EC | EN 60079-0:2012 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
IECEx approval | IECEx BAS 13.0046 | |
Approved for | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I |